GENERAL SPECIFICATION

Product Name Zinc Oxide Gapless Surge Arrester
Catalogue Number YH10W-27
Standard IEEE/IEC
Application Distribution
Color Gray Housing
Material Polymer
Shed Large-Small Shed
Packing 3pcs Arresters / Per Carton ( Standard)
Fumigation-free Wooden Pallets are Available

ELECTRICAL RATEING

Rated voltage of lightning arrester 27kV
Frequency Rating 48-62Hz
Rated discharge current rating 10kA
Maximum continuous operating voltage 22kV
DC 1mA reference voltage ≥41kV
8/20μs lightning current impulse residual voltage ≤81 kV
Creepage distance 850mm

ACCESSORIES

Earth Lead Wire Provide
Disconnector Provide
Insulated Bracket Provide
Galvanized Steel Mounting Bracket Optional